Danfoss TripleLynx CN Manual de Instalação Página 91

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 268
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 90
Connecting the inverters
WINAICO
Solar-Log
1000/500/200
Installation 91 of 268
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
Connect using the RS485 data cable with RJ45 plug;
Connection cables between the inverters are supplied with the invert-
ers. Use these.
Where to connect: RJ45 socket on the outside of the inverter
Procedure
1 Insert the RJ45 plug into the free RJ45 socket on inverter 1.
2 Insert the other end of the wire into any RJ45 socket on inverter 2.
3 Connect the other inverters to each other in the same way.
4 Terminate in the last inverter:
Insert the connection plug into the free RJ45 socket.
Allocating communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the rotating switch on the inverter interface card.
Procedure: As set out in the inverter's instructions
4.40 WINAICO
Interface not integrated. Retrofit RS485 interface card.
4 pin wiring
Communication address must be allocated.
Work steps
Allocate communication address
Switch off the inverters and the SolarLog™; Page 17
Install the RS485 interface in the inverter
Connect inverters to the Solar-Log
Connect the inverters to each other
Allocating communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the DIP switch on the interface card.
Before installing the RS485 interface card:
Allocate the communication address using the 8 interface card DIP switch-
es:
Vista de página 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 267 268

Comentários a estes Manuais

Sem comentários