Connecting the inverters
Schüco SGI series (RS485)
48 of 268 Solar-Log
1000/500/200
Installation
Procedure
1 If you are fabricating the cable yourself, connect the wires as shown in the
following diagram:
Solar-Log™ terminal block connector
2 Open the unit cover on the bottom of the inverter.
3 Insert the RJ45 plug into the RJ45 socket on the inverter.
4 If only one inverter is to be connected it must be terminated:
Insert the IP20 terminal plug into a free RJ45 socket (not strictly required
for cables up to 100 m long).
5 Insert the terminal block connector into the Solar-Log™ RS485 socket.
6 Close the unit cover on the bottom of the inverter.
Connecting the inverters to each other (Solar-Log
500
, Solar-Log
1000
)
Connect using a network cable (patch cable)
Where to connect: RJ45 sockets on the bottom of the inverter
Procedure
1 Open the unit cover on the bottom of the inverter.
2 Insert the RJ45 plug into any RJ45 socket on inverter 1.
3 Insert the other end of the wire into any RJ45 socket on inverter 2.
4 Connect the other inverters to each other in the same way.
5 Terminate in the last inverter:
Insert the IP20 terminal plug into a free RJ45 socket (not strictly required
for cables up to 100 m long).
6 Close the unit cover on the bottom of the inverter.
Allocating communication address
Recommendation: Continuous numbering starting with 1.
Setting: Using the inverter operating display
Procedure: As set out in the inverter's instructions