8-53 Start Select
Option: Function:
[2] Logic AND Activates Start command via the serial communi-
cation port, AND additionally via one of the
digital inputs.
[3] * Logic OR Activates Start command via the serial communi-
cation port OR via one of the digital inputs.
8-54 Reversing Select
Option: Function:
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the serial communication port.
NOTE
This parameter is active only when
8-01 Control Site is set to [0] Digital and
control word.
[0] * Digital
input
Activates Reverse command via a digital input.
[1] Bus Activates Reverse command via the serial
communication port.
[2] Logic AND Activates Reverse command via the serial
communication port, AND additionally via one of
the digital inputs.
[3] Logic OR Activates Reverse command via the serial
communication port OR via one of the digital
inputs.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the serial communication port.
NOTE
This parameter is active only
when8-01 Control Site is set to [0] Digital
and control word.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial
communication port.
[2] Logic AND Activates the set-up selection via the serial
communication port, AND additionally via one of
the digital inputs.
[3] * Logic OR Activate the set-up selection via the serial
communication port OR via one of the digital
inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter Preset
Reference selection via the terminals (digital
input) and/or via the serial communication port.
[0] Digital
input
Activates Preset Reference selection via a digital
input.
[1] Bus Activates Preset Reference selection via the
serial communication port.
[2] Logic AND Activates Preset Reference selection via the
serial communication port, AND additionally via
one of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the
serial communication port OR via one of the
digital inputs.
3.8.4 8-7* BACnet
8-70 BACnet Device Instance
Range: Function:
1 * [0 - 0x3FFFFEUL. ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range: Function:
127.0 * [0.0 - 127.0 ] Define the address of the master which
holds the highest address in this network.
Decreasing this value optimises polling for
the token.
8-73 MS/TP Max Info Frames
Range: Function:
1.0 * [1.0 - 65534.0 ] Define how many info/data frames the
device is allowed to send while holding
the token.
8-74 "I am" Service
Option: Function:
[0] * Send at power-
up
[1] Continuously Choose whether the device should send
the "I-Am" service message only at power-
up or continuously with an interval of
approx. 1 min.
8-75 Intialisation Password
Range: Function:
admin * [1 - 1 ] Enter the password needed for execution of
Drive Re-initialisation.
Parameters VLT HVAC Basic Drive Programming Guide
48 MG.18.B1.02 - VLT
®