5-12 Terminal 27 Digital Input
Parameter for configuring the input function on input terminal 27.
Option: Function:
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
5-13 Terminal 29 Digital Input
Parameter for configuring the input function on input terminal 29.
Option: Function:
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick Stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] * Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire mode
[52] Run permissive
[53] Hand Start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
3.6.3 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option: Function:
[0] * No operation Default for both relays
[1] Control ready Control board receives supply voltage.
[2] Drive ready Frequency converter is ready for
operation and applies supply signal on
control board.
[3] Drive ready/
remote control
Frequency converter is ready for
operation in Auto On-mode.
[4] Standby / no
warning
Frequency converter is ready for
operation. No start or stop command is
given. No warnings are present.
[5] VLT running Motor is running.
[6] Running / no
warning
Motor runs, and no warning are present.
[7] Run in range/no
warning
Motor runs within programmed current
ranges, see 4-50 Warning Current Low and
4-51 Warning Current High. No warnings
are present.
[8] Run on ref/no
warning
Motor runs at reference speed and with
no warnings.
[9] Alarm An alarm activates output.
[10] Alarm or
warning
An alarm or warning activates output.
[12] Out of current
range
Motor current is outside range set in
4-50 Warning Current Low and
4-51 Warning Current High.
[13] Below current,
low
Motor current is lower than set in
4-50 Warning Current Low.
[14] Above current,
high
Motor current is higher than set in
4-51 Warning Current High.
[21] Thermal warning The thermal warning turns on when the
temperature exeeds the limit in motor,
frequency converter or thermistor.
[22] Ready, no
thermal warning
Frequency converter is ready for
operation and no over-temperature
warning is present.
[23] Remote, ready,
no thermal
warning
Frequency converter is ready for
operation in Auto mode, and no over-
temperature warning is present.