3 Parameters
3.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the LCP buttons and config-
uration of the LCP display.
3.1.1 0-0* Basic Settings
0-01 Language
Option: Function:
Defines the language to be used in the display.
[0] * English
[1] Deutsch
[2] Francais
[3] Dansk
[4] Spanish
[5] Italiano
[28] Bras.port
[255] No Text
0-03 Regional Settings
Option: Function:
This parameter cannot be adjusted while the
motor is running. In order to meet the needs for
different default settings in different parts of the
world, 0-03 Regional Settings is implemented in
the frequency converter. The selected setting
influences the default setting of the motor
nominal frequency.
[0] * Interna-
tional
Sets default value of 1-23 Motor Frequency
[50Hz].
[1] North
America
Sets the default value of 1-23 Motor Frequency to
60Hz.
0-04 Operating State at Power-up
Option: Function:
Select the operating mode upon reconnection of
the frequency converter to mains voltage after
power down when operating in Hand (local)
mode.
[0] * Resume Resumes operation of the frequency converter
maintaining the same local reference and the
same start/stop condition (applied by [Hand On]/
[Off] on the LCP or Hand Start via a digital input
as before the frequency converter was powered
down.
0-04 Operating State at Power-up
Option: Function:
[1] Forced
stop,
ref=old
Uses saved reference [1] to stop the frequency
converter but at the same time retain the local
speed reference in memory prior to power down.
After mains voltage is reconnected and after
receiving a start command (using the LCP [Hand
On] button or Hand Start command via a digital
input) the frequency converter restarts and
operates at the retained speed reference.
0-06 GridType
Option: Function:
Select the grid type of the supply
voltage/frequency.
NOTE
Not all choices are supported in
all power sizes.
IT grid is a supply mains, where there
are no connections to ground.
Delta is a supply mains where the
secondary part of the transformer is
delta connected and one phase is
connected to ground.
[0] 200-240V/50Hz/IT-
grid
[1] 200-240V/50Hz/Delta
[2] 200-240V/50Hz
[10] 380-440V/50Hz/IT-
grid
[11] 380-440V/50Hz/Delta
[12] 380-440V/50Hz
[20] 440-480V/50Hz/IT-
grid
[21] 440-480V/50Hz/Delta
[22] 440-480V/50Hz
[30] 525-600V/50Hz/IT-
grid
[31] 525-600V/50Hz/Delta
[32] 525-600V/50Hz
[100] 200-240V/60Hz/IT-
grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-
grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
Parameters VLT HVAC Basic Drive Programming Guide
20 MG.18.B1.02 - VLT
®
is a registered Danfoss trademark
3
3