Installation Guide AFP/VFG 2(21) DN 15-250
DEN-SMT/SI VI.CA.K2.1I District Energy
LANGUAGEENGLISH
Safety Notes
Prior to assembly and commissioning to
avoid injury of persons and damages of
the devices, it is absolutely necessary to
carefully read and observe these instructions.
Necessary assembly, start-up, and maintenance
work must be performed only by qualified,
trained and authorized personnel.
Prior to assembly and maintenance work on the
controller, the system must be:
- depressurized,
- cooled down,
- emptied and
- cleaned.
Please comply with the instructions of the
system manufacturer or system operator.
Disposal instructions
This product should be
dismantled and its components
sorted, if possible, in various
groups before recycling or
disposal.
Always follow the local disposal regulations.
Definition of Application
The controller is used for diffe rential pressure
control of water and water glycol mixtures for
heating, district heating and cooling systems.
The technical data on the ra ting plates
determine the use.
Scope of Delivery
*) Impulse tube AF, accessory
Assembly
Admissible Installation Positions
DN 15-80 :
medium temperatures up to 120 °C:
Can be installed in any positi on.
DN 100-250 and DN 15-80 :
medium temperatures > 120 °C.
Installation permitted only in horizontal
pipelines with the actuator oriented
downwards.
Installation Location and Installation
Scheme
Return mounting
Flow mounting
Valve Installation
1. Install strainer before the controller.
2. Rinse system prior to installing the valve.
3. Observe flow direction on valve body.
Flanges in the pipeline must be in
parallel position and sealing surfaces
must be clean and without any damage.
4. Install valve.
5. Tighten screws crosswise in 3 steps up to the
max. torque.
Valve Actuator Installation
Valves DN 150-250
The actuator stem must be screwed into
the valve stem.
Observe the Installation In structions for the
valves DN 150-250.
Valves DN 15-125
1. Place actuator at the valve.
2. Align actuator, observe position of impulse
tube connection to the valve
3. Tighten union nut Torque 100 Nm
Impulse Tube mounting
When installing seal pots ❻①, please
observe the Installati on Instructions for
the seal pots.
• Whichimpulsetubestouse?
The impulse tube set AF (2×) ❻② can be
used: Order No.: 003G1391
or use the following pipes:
Stainless steel Ø 10×0,8
DIN 17458,
DIN 2391
Steel Ø 10×1 DIN 2391
Copper Ø 10×1 DIN 1754
• Connection of impulse tubes in the
system
Installation in return flow
Installation in supply flow
• Connection to the pipeline
No connection downwards , could be
chocked by dirt.
• ImpulseTubeInstallation(Copper)
1. Cut pipe into rectangular sections and
deburr.
2. Insert sleeves on both sides.
3. Verify the correct position of the cutting
ring .
4. Press impulse tube into the threaded
joint up to its stop.
5. Tighten union nut . Torque 40 Nm
Insulation
For medium temperatures up to 100 °C the
pressure actua tor may be insulated .
Dimensions
Flanges: connection dimensi ons acc. to
DIN 2501, seal form C
Dismounting
Danger
Danger of injury by hot water
Valve without actuator is open , Seal is in
the ac tuator.
Prior to dismounting depres surize system!
Carry out dismounting in re verse order to
mounting.
Leak and Pressure Test
Pressure must be constantly increased
at the +/ connec tion . Never increase
− pressure above + pressure.
Observe max. permitted pressure, see below.
Non-compliance may cause damages at the
actuator or valve.
Max. test pressure [bar] with connected
impulse tu bes
AFP cm
2
80 250 630
bar 25 25 16
In case of higher test pressu res, remove impulse
tubes at the pipelines .
Close connections with plugs G ¼ ISO 228.
Observe nominal pressure of the valve.
Max. test pres sure is 1,5 × PN
Filling the System, Start-up
The return flow pressure must not
exceed the supply flow pressure .
Non-compliance may cause damages at the
controller .
1. Open shut-off devices that are possibly
available at the impulse tubes.
2. Slowly open valves in the system.
3. Slowly open shut-off devices in the
supply flow.
4. Slowly open shut-off devices in the return
ow.
Putting out of Operation
1. Slowly close shut-off devices in the supply
ow.
2. Slowly close shut-off devices in the return
ow.
Differential Pressure Setting
Set-point range see rating plate
1. Start-up of system, see section .
2. Set flow rate on a motorised valve by
which the differential pressure is controlled,
to about 50 %
3. Adjustment
• Observepressureindicators.
• Turningtotheright increases the set-
point (stressing the spring)
• Turningtotheleft redu ces the
set-point (unstressing the spring)
4. The set-point adjuster may be sealed.