1.2.5 Disposal Instruction
Equipment containing electrical components
must not be disposed of together with domestic
waste.
It must be separately collected with electrical
and electronic waste according to local and
currently valid legislation.
1.3 Installation
1.3.1 Before Starting Repair Work
1. Disconnect FC101 from mains (and external DC
supply, if present.)
2. Wait as stated in the table below for discharge of
the DC-link:
Voltage (V) Power range (kW) Min. waiting time
(minutes)
3 x 200 0.25 3.7 4
3 x 200 5.5 45 15
3 x 400 0.37 7.5 4
3 x 400 11 90 15
3 x 600 2.2 7.5 4
3 x 600 11 90 15
3. Remove motor cable
1.3.2 Side-by-Side Installation
The frequency converter can be mounted side-by-side and requires the clearance above and below for cooling.
Power Clearance above/
below (mm/inch)
Frame IP class 3 x 200-240 V 3 x 380-480 V 3 x 525-600 V
H1 IP20 0.25-1.5 kW/0.33-2 Hp 0.37-1.5 kW/0.5-2 Hp 100/4
H2 IP20 2.2 kW/3 Hp 2.2-4 kW/3-5.4 Hp 100/4
H3 IP20 3.7 kW/5 Hp 5.5-7.5 kW/7.5-10 Hp 100/4
H4 IP20 5.5-7.5 kW/7.5-10 Hp 11-15 kW/15-20 Hp 100/4
H5 IP20 11 kW/15 Hp 18.5-22 kW/25-30 Hp 100/4
H6 IP20 15-18.5 Kw/20-25 Hp 30-45 kW/40-60 Hp 22-30 kW/30-40 Hp 200/7.9
H7 IP20 22-30 kW/30-40 Hp 55-75 kW/100-120 Hp 45-55ø W/60-100 Hp 200/7.9
H8 IP20 37-45 kW/50-60 Hp 90 kW/125 Hp 75-90 kW/120-125 Hp 225/8.9
H9 IP20 2.2-7.5 kW/3-10 Hp 100/4
H10 IP20 11-15 kW/15-20 Hp 200/7.9
NOTE
With IP21/Nema Type1 option kit mounted, a distance of 50 mm between the units is required.
Quick Guide VLT HVAC Basic Drive Quick Guide
4 MG18A302 - VLT
®