Circuit Breaker
Fuse
UL Non UL UL Non UL
Bussman
n
Bussman
n
Bussman
n
Bussman
n
Max fuse
Power kW Type RK5 Type RK1 Type J Type T Type G
3 x 525 - 600 V
IP20
2.2
KTS-R20
20
3 KTS-R20 20
5.5 KTS-R20 20
7.5 KTS-R20 30
11
KTS-R30 35
15 KTS-R30 35
22
Cutler-Hammer
EGE3080FFG
Cutler-Hammer
EGE3080FFG
FRS-R-80 KTN-R80 80
30 FRS-R-80 KTN-R80 80
45
Cutler-Hammer
JGE3125FFG
Cutler-Hammer
JGE3125FFG
FRS-R-125 KTN-R125 125
55 FRS-R-125 KTN-R125 125
75
Cutler-Hammer
JGE3200FAG
Cutler-Hammer
JGE3200FAG
FRS-R-200 KTN-R200 200
90 FRS-R-200 KTN-R200 200
3 x 380 - 480 V
IP54
0.75
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
Moeller NZMB1-A125
125
30 125
37 125
45
Moeller NZMB2-A160
160
55 160
75
Moeller NZMB2-A250
200
90 200
Table 1.3 Fuses
1.3.7
EMC-Correct Electrical Installation
General points to be observed to ensure EMC-correct
electrical installation.
•
Use only screened/armoured motor cables and
screened/armoured control cables.
•
Connect the screen to earth at both ends.
•
Avoid installation with twisted screen ends
(pigtails), since this ruins the screening effect at
high frequencies. Use the cable clamps provide-
dinstead.
•
It is important to ensure good electrical contact
from the installation plate through the installation
screws to the metal cabinet of the frequency
converter.
•
Use starwashers and galvanically conductive
installation plates.
•
Do not use unscreened/unarmoured motor cables
in the installation cabinets.
Quick Guide VLT HVAC Basic Drive Quick Guide
16 MG18A302 - VLT
®
is a registered Danfoss trademark
11