VLT
®
6000 HVAC
80
★ = factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
MG.60.B1.02 - VLT is a registered Danfoss trade mark
013 OFF/STOP on LCP (STOP BUTTON)
Value:
Disable (DISABLE) [0]
★ Enable (ENABLE) [1]
Function:
This parameter allows selection/deselection of the
local stop key on the control panel.
Description of choice:
If Disable [0] is selected in this parameter, the [OFF/
STOP] key will be inactive.
NB!
If Disable is selected, the motor cannot be
stopped by means of the [OFF/STOP] key.
014 Auto start on LCP (AUTO START BTTN)
Value
Disable (DISABLE) [0]
★ Enable (ENABLE) [1]
Function:
This parameter allows selection/deselection of the
auto start key on the control panel.
Description of choice:
If Disable [0] is selected in this parameter, the [AUTO
START] key will be inactive.
015 Reset on LCP (RESET BUTTON)
Value:
Disable (DISABLE) [0]
★ Enable (ENABLE) [1]
Function:
This parameter allows selection/deselection of the
reset key on the control panel.
Description of choice:
If Disable [0] is selected in this parameter, the [RESET]
key will be inactive.
NB!
Only select Disable [0] if an external reset
signal has been connected via the digital
inputs.
016 Lock for data change
(DATA CHANGE LOCK)
Value:
★ Not locked (NOT LOCKED) [0]
Locked (LOCKED) [1]
Function:
This parameter allows the control panel to be ‘locked’,
which means that it is not possible to carry out data
modifications via the control unit.
Description of choice:
If Locked [1] is selected, data modifications in the
parameters cannot be made, although it will still be
possible to carry out data modifications via the bus.
Parameters 007-010 Display readout can be changed
via the control panel.
It is also possible to lock for data modifications in
these parameters by means of a digital input, see
parameters 300-307 Digital inputs on page 97.
017 Operating state at power up, local
control (POWER UP ACTION)
Value:
★ Auto restart (AUTO RESTART) [0]
OFF/Stop (OFF/STOP) [1]
Function:
Setting of the desired operating mode when the
mains voltage is reconnected.
Description of choice:
Auto restart [0] is selected if the VLT frequency con-
verter is to start up in the same start/stop condition
as immediately before power to the converter is cut off.
OFF/Stop [1] is selected if the VLT frequency con-
verter is to remain stopped when the mains voltage is
connected, until a start command is active. To restart,
activate the key [HAND START] or [AUTO START]
by
using the control panel.
NB!:
If [HAND START] or [AUTO START] cannot be
activated by the keys on the control panel (see
parameter 012/014 Hand/Auto start on LCP) the
motor will not be able to restart if OFF/Stop [1] is
selected.
If Handstart or Autostart has been programmed for
activation via the digital inputs, the motor will not be
able to restart if OFF/Stop [1] is selected.