Danfoss VLT 6000 HVAC Manual de Serviço Página 39

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 177
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 38
VLT
®
6000 HVAC
39MG.60.B1.02 - VLT is a registered Danfoss trademark
Introduction to
HVAC
LC filters 6002-6006, 200 - 240 V / 6002-6011 380 - 460 V
The drawing on the left gives the measurements of IP
20 LC filters for the above-mentioned power range.
Min. space above and under enclosure: 100 mm.
IP 20 LC filters have been designed for side-by-side
installation without any space between enclosures.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
- EN 55011-1B: Max. 50 screened/armoured cable
Bookstyle: Max. 20 m screened/armoured cable
- EN 55011-1A: Max. 150 m screened/armoured cable
Weight: 175Z0825 7.5 kg
175Z0826 9.5 kg
175Z0832 9.5 kg
Installation of LC filter IP 20 Bookstyle
Installation of LC filter IP 20
LC filter
LC filter
VLT
VLT
Vista de página 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 176 177

Comentários a estes Manuais

Sem comentários