Danfoss VLT 6000 HVAC Manual de Serviço Página 54

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 177
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 53
VLT
®
6000 HVAC
54
MG.60.B1.02 - VLT is a registered Danfoss trade mark
EMC-correct electrical installation
General points to be observed to ensure EMC-correct
electrical installation:
- Use only screened/armoured motor cables and
screened/armoured control cables.
- Connect the screen to earth at both ends.
- Avoid installation with twisted screen ends
(pigtails), since this ruins the screening effect at
high frequencies. Use cable clamps instead.
- It is important to ensure good electrical contact
from the installation plate through the installation
screws to the metal cabinet of the VLT frequency
converter.
- Use toothed discs and galvanically conductive
installation plates.
- Do not use unscreened/unarmoured motor cables
in the installation cabinets.
The illustration below shows EMC-correct electrical
installation; the VLT frequency converter has been
fitted in an installation cabinet and connected to a
PLC.
Vista de página 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 176 177

Comentários a estes Manuais

Sem comentários