8 Manual RS8DY302 © Danfoss 07-2005 EKC 102
Functions
Function No.
Normal display
Normal display shows the temperature value from the
thermostat sensor Sair.
Thermostat
Set point
Regulation is based on the set value. The value is set via a
push on the centre button.
The set value can be locked or limited to a range with the
settings in r02 and r03.
Differential
When the temperaure is higher than the reference + the
set differential, the compressor relay will be cut in. It will
cut out again when the temperature comes down to the
set reference.
r01
Setpoint limitation
The controller’s setting range for the setpoint may be
narrowed down, so that much too high or much too low
values are not set accidentally - with resulting damages.
To avoid a too high setting of the setpoint, the max. al
-
lowable reference value must be lowered.
r02
To avoid a too low setting of the setpoint, the min. allow
-
able reference value must be increased.
r03
Correction of the display’s temperature showing
If the temperature at the products and the temperature
received by the controller are not identical, an offset
adjustment of the shown display temperature can be
carried out.
r04
Temperature unit
Set here if the controller is to show temperature values in
°C or in °F.
r05
Correction of signal from Sair
Compensation possibility through long sensor cable.
r09
Start / stop of refrigeration
With this setting refrigeration can be started, stopped or
a manual override of the outputs can be allowed.
1 = regulation
0 = regulation is stopped
-1 = regulation is stopped - override allowed.
Stopped regulation will give a "Standby alarm".
r12
Night setback value
The thermostat’s reference will be the setpoint plus this
value when the controller changes over to night opera
-
tion. (Select a negative value if the function is used for
quick cooling”.)
r13
Alarm
The controller can give alarm in different situations.
When there is an alarm all the light-emitting diodes (LED)
will flash on the controller front panel
Alarm delay (short alarm delay)
If one of the two limit values is exceeded, a timer func
-
tion will commence. The alarm will not become active
until the set time delay has been passed. The time delay
is set in minutes.
A03
Time delay for door alarm
The time delay is set in minutes.
The function is defined in o02.
A04
Ref. Dif.
Time delay for cooling (long alarm delay)
This time delay is used during start-up (recovery time),
during defrost, in the cooling phase after a defrost.
There will be change-over to the normal time delay (A03)
when the temperature has dropped below the set upper
alarm limit.
The time delay is set in minutes.
A12
Upper alarm limit
Here you set when the alarm for high temperature is to
start. The limit value is set in °C (absolute value). The limit
value will be raised during night operation. The value is
the same as the one set for night setback, but will only
be raised if the value is positive.
A13
Lower alarm limit
Here you set when the alarm for low temperature is to
start. The limit value is set in °C (absolute value).
A14
High alarm limit for condenser temperature
If the Saux sensor is used for monitoring the condenser’s
temperature you must set the value at which the alarm
is to become activated. The value is set in °C. There is
no alarm delay. The alarm disappears again when the
temperature has dropped 10 degrees. Definition of Saux
takes place in o69.
A37
Compressor
The compressor relay works in conjunction with the
thermostat. When the thermostat calls for refrigeration
will the compressor relay be operated.
Running times
To prevent irregular operation, values can be set for the
time the compressor is to run once it has been started.
And for how long it at least has to be stopped.
The running times are not observed when defrosts start.
Min. ON-time (in minutes)
c01
Min. OFF-time (in minutes)
c02
Time delay for couplings of two compressors
Settings indicate the time that has to elapse from the
first relay cuts in and until the next relay has to cut in.
c05
Reversed relay function for compressor relay
0: Normal function where the relay cuts in when refrig-
eration is demanded
1: Reversed function where the relay cuts out when
refrigeration is demanded (this wiring produces the
result that there will be refrigeration if the supply volt-
age to the controller fails). (When two compressors are
cut in and out the two relays will operate in opposite
directions).
c30
Defrost
The controller contains a timer function that is zeroset
after each defrost start.
The timer function will start a defrost if/when the interval
time is passed.
The timer function starts when voltage is connected to
the controller, but it is displaced the first time by the set
-
ting in d05.
This timer function can be used as a simple way of star-
ting defrosts, but it will always act as safety defrost if one
of the subsequent defrost starts is not received.
Defrost start can also be accomplished via contact sig
-
nals or manual start-up.
All starting methods will function in the controller. The
different functions have to be set, so that defrosts do not
come tumbling” one after the other.
Defrost can be accomplished with electricity or natural
defrost.
The actual defrost will be stopped based on time or tem-
perature with a signal from a temperature sensor.
Here is a description of the individual functions.
A controller only contains this part of the functions. Cf. the menu
survey.