6 Manual RS8DY302 © Danfoss 07-2005 EKC 102
Menu survey
SW = 1.1x
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you reconnect the supply voltage
EKC 102A
Parameters
Min.-
value
Max.-
value
Factory
setting
Actual
setting
Function Codes
Normal operation
Temperature (set point)
--- -50°C 99°C 2°C
Thermostat
Differential
r01 0,1 K 20 K 2 K
Max. limitation of setpoint setting
r02 -49°C 99°C 99°C
Min. limitation of setpoint setting
r03 -50°C 99°C -50°C
Adjustment of temperature indication
r04 -20 K 20 K 0 K
Temperature unit (°C/°F)
r05 °C °F °C
Correction of the signal from Sair
r09 -10 K 10 K 0 K
Manual service (-1), stop regulation (0), start regulation (1)
r12 -1 1 1
Compressor
Min. ON-time
c01 0 min 30 min 0 min
Min. OFF-time
c02 0 min 30 min 0 min
Compressor relay must cutin and out inversely
(NC-function)
c30 OFF On OFF
Defrost
Defrost method (0=none / 1=natural)
d01 0 1 1
Defrost stop temperature
d02 0°C 25°C 6°C
Interval between defrost starts
d03 0 hours 48 hours 8 hours
Max. defrost duration
d04 0 min 180 min 45 min
Displacement of time on cutin of defrost at start-up
d05 0 min 240 min 0 min
Defrost sensor (0=time, 1=Sair)
d10 0 1 0
Defrost at start-up
d13 no yes no
Miscellaneous
Delay of output signals after start-up
o01 0 s 600 s 5 s
Access code
o05 0 100 0
Used sensor type (Pt /PTC/NTC)
o06 Pt ntc Pt
Refrigeration or heat (rE=refrigeration, HE=heat)
o07 rE HE rE
Display step = 0.5 (normal 0.1 at Pt sensor)
o15 no yes no
Save the controllers present settings to the programming
key. Select your own number.
o65 0 25 0
Load a set of settings from the programming key (previ-
ously saved via o65 function)
(Can only be set when regulation is stopped (r12=0)
o66 0 25 0
Replace the controllers factory settings with the present
settings
o67 OFF On OFF
Service
Status on relay
Can be controlled manually, but only when r12=-1
u58
Fault code display
A45 Standby mode
Alarm code display
E1 Fault in controller
E29 Sair sensor error
Status code display
S0 Regulating
S2 ON-time Compressor
S3 OFF-time Compressor
S11 Refrigeration stopped by thermostat
S14 Defrost sequence. Defrosting
S20 Emergency cooling
S32 Delay of output at start-up
non The defrost temperature cannot be
displayed. There is no sensor
-d- Defrost in progress / First cooling
after defrost
PS Password required. Set password
Regulation starts when the voltage is
on.