Vista de página 34
Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
35
VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Wiring - 230 V a.c.
ECL Comfort 310 wiring example
Supply voltage 230 V a.c. - 50 Hz
Voltage range 207 to 244 V a.c. (IEC 60038)
Power consumption 5 VA
Max. load on relay outputs 4(2) A - 230 V a.c. (4 A for ohmic load,
2 A for inductive load)
Max. load on actuator outputs 0.2 A - 230 V a.c.
Wiring - 24 V a.c.
ECL Comfort 310 wiring example
Auxiliary relays (K) must be used in order to separate the 230 V a.c. supply from the 24 V a.c. supply of the controller.
Supply voltage 24 V a.c. - 50 Hz
Voltage range 21.6 to 26.4 V a.c. (IEC 60038)
Power consumption 5 VA
Max. load on relay output 4(2) A - 24 V a.c. (4 A for ohmic load,
2 A for inductive load)
Max. load on actuator output 1 A - 24 V a.c.