Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
33
VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
ECL 485 communication bus data:
Purpose For internal ECL Comfort 210 / 310 and ECA 30 / 31 use only
(Danfoss proprietary bus)
Connection Terminals in base part
Non-galvanic isolated
Cable type Shielded cable, 2 x twisted pair,
Min. cross section: 0,22 mm (AWG 24).
Examples:
LiYCY 2 × 2 × 0.25 mm2 (AWG 24) or Ethernet CAT5
Max. total cable length (bus cable + sensor cables) 200 m in total (inclusive sensor cables)
Max. number of ECL slaves connected Units with unigue address (1 - 9): 9
Units with address “0”: 5
Max. number of Remote Control Units connected 2
Data sent from master Date
Time
Outdoor temperature
Desired room temperature
DHW-priority signal
Data sent from addressed slave controller Desired ow temperature from each circuit
Data sent from ECA 30 / 31
• Actual and desired room temperature
• Function selector mode
• (ECA 31) Relative humidity
Modbus communication data:
Purpose For SCADA system
Connection Terminals 34 and 35 in base part. Modbus reference
(terminal 36) must be connected.
Galvanic isolated (500 V).
Protocol Modbus RTU
Cable type Shielded cable, 2 x twisted pair + Signal GND.
Min. cross section: 0,22 mm2 (AWG 24).
Example: LiYCY 2 × 2 × 0.25 mm2 (AWG 24)
Max. bus cable length 1200 m (dependent on cable type and installation).
Communication speed Half duplex.
9,6 Kbit/s (default) / 19.2 Kbit/s / 38.4 Kbit/s
Serial mode 8 data bit, even parity and 1 stop bit.
Network According to the standard Modbus Serial Line
Implementation Guide V1.0.
M-bus communication data:
Purpose Connection to heat meters, max. 5 heat meters
Connection Terminals 37 and 38 in base part.
Non-galvanic isolated
M-Bus master according to DS / EN 1434-3: 1997
Cable type 2 x 0,8 mm2
Example: JY(St)Y 2 x 0.8 mm2 (not twisted pair)
Max. cable length 50 m
Baud rate 300 baud (adjustable)
Update time 60 s (adjustable)
Gateway function Allows the ECL Portal to read energy meters directly
Supported heat meters Infocal 6 and many other marks and types.
Information about other heat meters on request
Transmitted heat meter data Heat meter type dependent:
• Primary ow temperature
• Primary return temperature
• Actual ow / accumulated ow
• Actual heat / power
• Accumulated heat energy
Recommendations: Danfoss recommends 230 V a.c. supplied heat meters
USB communication data:
USB CDC (Communication Device Class) For service purposes
(Windows driver is needed, to enable that Windows recognize
the ECL as a virtual COM port)
Modbus over USB Similar to the serial Modbus, but with relaxed timing
Connection, cable type Standard USB cable (USB A -------- USB B)