Data sheet ECL Comfort 310 controller, Remote Control Units ECA 30 / 31 and Application keys
2
VD.KT.X3.02 © Danfoss 04/2015
DEN-SMT/DK
Description (continued)
The enclosure is designed for mounting on wall
and DIN rail. A variant ECL Comfort 310B (without
display and dial) is available. It can be used for
mounting inside a panel and is operated by means
of the RCU ECA 30 / 31 which can be placed in front
of the panel.
The ECL Comfort 310 can work as a stand-alone
controller and communicate with up to two RCUs
and an extension module ECA 32 with additional
inputs / outputs.
The ECL Comfort 310 can also work with up to 2 x
RCUs, ECA 32 and other ECL Comfort 210 / 310
controllers via the ECL 485 communication bus.
Ethernet connection is integrated in the controller.
Furthermore, Modbus communication to SCADA
systems (Supervisory Control and Data Acquisition)
and M-bus communication to heat meters are
integrated.
ECL Application Key and applications:
Dierent ECL Application Keys make it easy for the
ECL Comfort 310 hardware to run dierent
applications. The ECL Comfort 310 controller is
loaded with the desired application by means of
the ECL Application Key, which contains
information about applications (basic application
sketches are shown in the display), languages and
factory settings.
The ECL Application Keys, series A2xx can be used
in ECL Comfort 210 and ECL Comfort 310. Most of
the A2xx application keys give extended
functionalities when used in ECL Comfort 310, such
as additional temperature sensors and M-bus
communication.
The ECL Application Keys, series 3xx can be used
in ECL Comfort 310 only.
The application parameters are stored in the
controller and are not aected by power break.
The relevant ECL Application Keys for the ECL
Comfort 210 / 310 controller can be found in the
ordering section.
Remote Control Unit (RCU):
The RCUs ECA 30 and ECA 31 are used for room
temperature control and override of the ECL
Comfort 310. The display has backlight. The RCUs
are connected to the ECL Comfort controllers by
means of 2 × twisted pair cable for communication
and power supply (ECL 485 communication bus).
The ECA 30 / 31 has a built-in room temperature
sensor. An external room temperature sensor can
be connected substituting the built-in temperature
sensor.
Furthermore, the ECA 31 has a built-in relative
humidity sensor and the signal is used in relevant
applications. It is possible to connect up to 2 RCUs
on the ECL 485 communication bus. One RCU can
monitor max. 10 ECL Comfort controllers (master/
slave system).