8.1.4 Mains Supply 3x525-690 V AC
Type Designation P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5
Typical Shaft Output [kW] 1.1 1.5 2.2 3.0 4.0 5.5 7.5
Enclosure IP20 (only) A3 A3 A3 A3 A3 A3 A3
Output current
Continuous (3x525-550 V) [A] 2.1 2.7 3.9 4.9 6.1 9.0 11
Intermittent (3x525-550 V) [A] 3.4 4.3 6.2 7.8 9.8 14.4 17.6
Continuous kVA (3x551-690 V) [A] 1.6 2.2 3.2 4.5 5.5 7.5 10
Intermittent kVA (3x551-690 V) [A] 2.6 3.5 5.1 7.2 8.8 12 16
Continuous kVA 525 V AC 1.9 2.5 3.5 4.5 5.5 8.2 10
Continuous kVA 690 V AC 1.9 2.6 3.8 5.4 6.6 9.0 12
Max. input current
Continuous (3x525-550 V) [A] 1.9 2.4 3.5 4.4 5.5 8.0 10
Intermittent (3x525-550 V) [A] 3.0 3.9 5.6 7.1 8.8 13 16
Continuous kVA (3x551-690 V) [A] 1.4 2.0 2.9 4.0 4.9 6.7 9.0
Intermittent kVA (3x551-690 V) [A] 2.3 3.2 4.6 6.5 7.9 10.8 14.4
Additional specifications
Estimated power loss at rated max. load [W]
4)
44 60 88 120 160 220 300
Max. cable cross section
5)
(mains, motor, brake
and load sharing) [mm
2
]/(AWG)
6, 4, 4 (10, 12, 12)
(min. 0.2 (24))
Max. cable cross-section with disconnect 6, 4, 4 (10, 12, 12)
Efficiency
3)
0.96 0.96 0.96 0.96 0.96 0.96 0.96
Table 8.7 Mains Supply 3x525-690 V AC - Normal overload 110% for 1 minute, P1K1-P7K5
Type Designation P11K P15K P18K P22K P30K
High/Normal Load NO NO NO NO NO
Typical Shaft Output at 550 V [kW] 7.5 11 15 18.5 22
Typical Shaft Output at 690 V [kW] 11 15 18.5 22 30
IP20/Chassis B4 B4 B4 B4 B4
IP21/NEMA 1 B2 B2 B2 B2 B2
IP55/NEMA 12 B2 B2 B2 B2 B2
Output current
Continuous (3 x 525-550 V) [A] 14 19 23 28 36
Intermittent (60 s overload) (3 x 525-550 V) [A] 22.4 20.9 25.3 30.8 39.6
Continuous (3 x 551-690 V) [A] 13 18 22 27 34
Intermittent (60 s overload) (3 x 551-690 V) [A] 20.8 19.8 24.2 29.7 37.4
Continuous kVA (550 V AC) [kVA] 13.3 18.1 21.9 26.7 34.3
Continuous kVA (690 V AC) [kVA] 15.5 21.5 26.3 32.3 40.6
Max. input current
Continuous (at 550 V) [A] 15 19.5 24 29 36
Intermittent (60 s overload) (at 550 V) [A] 23.2 21.5 26.4 31.9 39.6
Continuous (at 690 V) [A] 14.5 19.5 24 29 36
Intermittent (60 s overload) (at 690 V) [A] 23.2 21.5 26.4 31.9 39.6
Max. pre-fuses
1)
[A]
63 63 63 80 100
Additional specifications
Estimated power loss at rated max. load [W]
4)
150 220 300 370 440
Max. cable cross-section (mains/motor, load sharing and brake)
[mm
2
]/(AWG)
2)
35, 25, 25 (2, 4, 4)
Max. cable size with mains disconnect [mm
2
]/(AWG)
2)
16, 10, 10 (6, 8, 8)
Efficiency
3)
0.98 0.98 0.98 0.98 0.98
Table 8.8 Mains Supply 3 x 525-690 V AC - Normal overload 110% for 1 minute, P11K-P30K
Specifications
VLT
®
HVAC Drive Operating Instructions
MG11AJ02 - Rev. 2013-07-31 49