Recommended Initialisation Procedure, via
14-22 Operation Mode
1. Press [Main Menu] twice to access parameters.
2.
Scroll to 14-22 Operation Mode and press [OK].
3.
Scroll to Initialisation and press [OK].
4. Remove power to the unit and wait for the
display to turn off.
5. Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6. Alarm 80 is displayed.
7. Press [Reset] to return to operation mode.
Manual Initialisation Procedure
1. Remove power to the unit and wait for the
display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialisation does not reset the following frequency
converter information
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
5.4
Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic
motor and application parameters.
At first power up or after initialisation of the
frequency converter, SmartStart starts by itself.
Follow on-screen instructions to complete
commssioning of the frequency converter.
SmartStart can always be re-activiated by
selecting Quick Menu Q4 - SmartStart.
For commissioning without use of the SmartStart
wizard, refer to 5.4.2 Commissioning via [Main
Menu] or the Programming Guide.
NOTICE
Motor data are required for the SmartStart setup. The
required data are normally available on the motor
nameplate.
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-
up and checkout purposes. Application settings may vary.
Enter data with power ON, but before operating the
frequency converter.
1. Press [Main Menu] on the LCP.
2. Use the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
130BP066.10
1107 RPM
0 -
**
Operation/Display
1 -
**
Load/Motor
2 -
**
Brakes
3 -
**
Reference / Ramps
3.84 A 1 (1)
Main menu
Illustration 5.2 Main Menu
3. Use navigation keys to scroll to parameter group
0-0* Basic Settings and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Opperations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A 1(1)
130BP087.10
Illustration 5.3 Operation/Display
4.
Use navigation keys to scroll to 0-03 Regional
Settings and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A 1(1)
130BP088.10
Illustration 5.4 Basic Settings
5.
Use navigation keys to select [0] International or
[1] North America as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters).
6. Press [Main Menu] on the LCP.
Commissioning
VLT
®
HVAC Drive Operating Instructions
24 MG11AJ02 - Rev. 2013-07-31
55