VLT® 8000 AQUA
Installation
■ Bus connection
The serial bus connection in accordance with the RS
485 (2-conductor) norm is connected to terminals
68/69 of the AFD (signals P and N). Signal P is
the positive potential (TX+,RX+), while signal N
is the negative potential (TX-,RX-).
If more than one AFD is to be co
nnected to a given
master, use parallel connections.
In order to avoid potential equalizing currents in the
shield, the cable shield can be grounded via terminal
61, which is connected to the frame via an RC-link.
Bus termination
The bus must be terminated by a resistor network
at both ends. For this purpose, set switches 2
and 3 on the control card for "ON".