Data sheet ECL Comfort 200
5
VD.7B.A6.02 © Danfoss 11/2008
DH-SMT/DK
Wiring - 230 V a.c.
Supply voltage 230 V a.c. - 50 Hz
Voltage range 207 to 244 V a.c. (IEC 60038)
Power consumption 5 VA
Load on relay outputs 4(2) A - 230 V a.c.
Load on triac outputs 0.2 A - 230 V a.c.
Wiring - 24 V a.c.
Auxiliary relays (K1 and K2) must be used in order to
separate the 230 V a.c. supply from the 24 V a.c. supply of
the controller.
Supply voltage 24 V a.c. - 50 Hz
Voltage range 21.6 to 26.4 V a.c. (IEC 60038)
Power consumption 5 VA
Load on relay outputs 4(2) A - 24 V a.c.
Load on triac outputs 1 A - 24 V a.c.