Data sheet ECL Comfort 200
4
VD.7B.A6.02 © Danfoss 11/2008
DH-SMT/DK
Operation
Arrow buttons. Switch
between the lines of the ECL
Card.
Shift button. Switch between
temperatures, changeover
points etc.
Adjust temperatures and
values etc.
Switches between user
settings (yellow card side)
and service settings (grey
card side)
Controller mode
Manual operation (used only
at maintenance and service)
Automatic operation
Constant comfort
temperature
Constant reduced
temperature
Stand-by mode
User
setting
indicator
Service
setting
indicator
User /
service
settings
Change
of
display
Adjust-
ment
Controller
mode
The ECL Card
Display example:
8
0 36912 15 18 21 24
1
3
5
C
3
19
The display shows all status information about
the heating system. The time and the heating
program is shown in one of the displays which
can be selected as a favourite display. The display
is also used for the setting of control parameters.
Functions ECL Comfort 200 has a custom-designed display
with backlight for monitoring and setting.
The controller can be used as master or slave in
systems with master/slave controllers.
A remote control or room panel can be con-
nected to the system device bus.
Optional modules can be inserted into the
controller to obtain communication via MODBUS
or RS 232.
The Auto Tuning function for the automatic
setting of control parameters for instantaneous
domestic hot water production is available with
the ECL Card P16.
However, Auto Tuning is only applicable with
valves that are approved for Auto Tuning, i.e. the
Danfoss types VB 2 and VM 2 with split character-
istic as well as logarithmic valves such as VF and
VFS.
Motor protection, which ensures stable control
and a long life of the motorized valve, is available
with ECL Cards P16, P17 and P30.
General data
Ambient temperature 0 - 50 °C
Storage temperature -40 - + 70 °C
Mounting On wall, in panel or on DIN rail
Sensor type Pt 1000 (1000 ohm at 0 °C)
Grade of enclosure IP 41 - DIN 40050
- marking
in accordance with the standards
EMC-Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
EN61000-6-3 and EN61000-6-1,
Low Voltage Directive 73/23/EEC and 93/68/EEC