Danfoss C67 Guia do Utilizador Página 13

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 84
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 12
Installation
10.5a Indirectly connected heating system with
or without mixing loop and secondarily
connected storage tank
System settings
Circuit Line Description Recomm.
setting
I 17 Influence on desired flow temp. 3
I 51
DHW charging pump /
changeover valve
ON
I 53
Desired flow temperature at
DHW charging
OFF
I 67
Adaptive function of S2 flow
temperature during DHW
charging
20
I 140
Function of temperature sensor
S5
2
I 152
Max limitation temperature at
sensor S2 during DHW charging
70*
* Line 152 = desired charging temperature
Heating circuit II can only be operated against heating circuit I.
This means that heating circuit II cannot be supplied if heating
circuit I is deactivated.
10h
Vista de página 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 83 84

Comentários a estes Manuais

Sem comentários