Danfoss C37 Guia do Utilizador Página 45

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 78
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 44
The grey
side of the
ECL Card
Extended service
Service parameter(s) 20-21
32e
20 Optimization based on room / outdoor temperature
Circuit
Setting range Factory setting
(I) / (II)
ON / OFF (OFF) / (OFF)
The optimized start and stop time can be based on either room or
outdoor temperature.
ON: Optimization based on room temperature, if
measured.
OFF: Optimization based on outdoor
temperature. Use this setting if the room
temperature is not measured.
21 Total stop
Circuit Setting range Factory setting
I / (II) ON / OFF OFF / (OFF)
Decide whether you want a total stop during the setback
temperature period.
ON: The desired flow temperature is lowered
to 10 °C. The min. setting of the flow
temperature (line 2, section 22) is overruled.
Desired flow
temp. (°C)
10 °C
Time
OFF: No total stop
Desired flow
temp. (°C)
10 °C
Time
Vista de página 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 77 78

Comentários a estes Manuais

Sem comentários