Conversion index Conversion factor
74 0.1
2 100
1 10
0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
7.4.13 Process Words (PCD)
The block of process words is divided into two blocks of
16 bits, which always occur in the defined sequence.
PCD 1 PCD 2
Control (master slave Control word)
Reference-value
Control (slave master) Status word
Present output
frequency
7.5 Examples
7.5.1 Writing a Parameter Value
Change 4-14 Motor Speed High Limit [Hz] to 100Hz.
Write the data in EEPROM.
PKE = E19E Hex - Write single word in 4-14 Motor Speed
High Limit [Hz]:
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex
Data value 1000, corresponding to 100Hz, see
7.3.12 Conversion.
The telegram looks like this:
E19E H
PKE IND PWE
high
PWE
low
0000 H 0000 H 03E8 H
130BA092.10
Note: 4-14 Motor Speed High Limit [Hz] is a single word, and
the parameter command for write in EEPROM is “E”.
Parameter number 4-14 is 19E in hexadecimal.
The response from the slave to the master is:
119E H
PKE
IND
PWE
high
PWE
low
0000 H 0000 H 03E8 H
130BA093.10
7.5.2
Reading a Parameter Value
Read the value in 3-41 Ramp 1 Ramp up Time
PKE = 1155 Hex - Read parameter value in 3-41 Ramp 1
Ramp up Time
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
1155 H
PKE IND PWE
high
PWE
low
0000 H 0000 H 0000 H
130BA094.10
If the value in 3-41 Ramp 1 Ramp up Time is 10 s, the
response from the slave to the master is:
130BA267.10
1155 H
PKE
IND
0000 H 0000 H 03E8 H
PWE
high
PWE
low
3E8 Hex corresponds to 1000 decimal. The conversion
index for 3-41 Ramp 1 Ramp up Time is -2, i.e. 0.01.
3-41 Ramp 1 Ramp up Time is of the type Unsigned 32.
7.6
Modbus RTU Overview
7.6.1 Assumptions
Danfoss assumes that the installed controller supports the
interfaces in this document, and strictly observe all
requirements and limitations stipulated in the controller
and frequency converter.
7.6.2
What the User Should Already Know
The Modbus RTU (Remote Terminal Unit) is designed to
communicate with any controller that supports the
interfaces defined in this document. It is assumed that the
user has full knowledge of the capabilities and limitations
of the controller.
7.6.3
Modbus RTU Overview
Regardless of the type of physical communication
networks, the Modbus RTU Overview describes the process
a controller uses to request access to another device. This
process includes how the Modbus RTU responds to
RS-485 Installation and Set... VLT HVAC Basic Drive Design Guide
MG.18.C2.02 - VLT
®