Motor protection can be implemented using a range of
techniques: PTC sensor in motor windings; mechanical
thermal switch (Klixon type); or Electronic Thermal Relay
(ETR).
1330
550
250
-20°C
175HA183.10
4000
3000
R
(Ω)
nominel
nominel -5°C
nominel +5°C
[°C]
Using a digital input and 10V as power supply:
Example: The frequency converter trips when the motor
temperature is too high.
Parameter set-up:
Set 1-90 Motor Thermal Protection to Thermistor Trip [2]
Set 1-93 Thermistor Source to Digital Input 29 [6]
R
OFF
ON
<800 Ω >2.9 kΩ
18
19
12 20 55
27 29 42 45 50 53 54
DIGI IN
DIGI IN
DIGI IN
DIGI IN
61 68 69
N
P
COMM. GND
+24V
0/4-20mA A OUT / DIG OUT 0/4-20mA A OUT / DIG OUT
COM A IN
COM DIG IN
10V/20mA IN
10V/20mA IN
10V OUT
BUS TER.
OFF ON
130BB898.10
Using an analog input and 10V as power supply:
Example: The frequency converter trips when the motor
temperature is too high.
Parameter set-up:
Set 1-90 Motor Thermal Protection to Thermistor Trip [2]
Set 1-93 Thermistor Source to Analog Input 54 [2]
NOTE
Do not set Analog Input 54 as reference source.
18
19
12 20 55
27 29 42 45 50 53 54
DIGI IN
DIGI IN
DIGI IN
DIGI IN
61 68 69
N
P
COMM. GND
+24V
0/4-20mA A OUT / DIG OUT 0/4-20mA A OUT / DIG OUT
COM A IN
COM DIG IN
10V/20mA IN
10V/20mA IN
10V OUT
BUS TER.
OFF ON
130BB897.10
R
<3.0 k
>2.9k
OFF
ON
Input
Digital/analog
Supply Voltage
Volt
Threshold
Cut-out Values
Digital 10V
< 800 - > 2.9k
Analog 10V
< 800 - > 2.9k
NOTE
Check that the chosen supply voltage follows the specifi-
cation of the used thermistor element.
Summary
With the ETR the motor is protected for being over heated
and there is no need for any further motor protection.
That means when the motor is heated up the ETR timer
controls for how long time the motor can be running at
the high temperature before it is stopped in order to
prevent over heating. If the motor is overloaded without
reaching the temperature where the ETR shuts of the
motor.
ETR is activated in 1-90 Motor Thermal Protection.