2.1.1. View
Menu Structure - View
Parameter Description
Mode: On grid Displays present inverter mode. See operation mode definitions
Prod. today: 12345 kWh Energy production today in kWh. Value from inverter or S0 energy-meter
Output Power: 12345 W Current output power in Watt
[ --- utilization bar --- ] Shows level of inverter utilisation as % of max. utilisation
Table 2.1: View
2.1.2. View 2
Pressing F1 once more will result in the following screen being shown (see section on buttons
for more information):
Menu Structure - View 2
Parameter Description
Grid mgmt:
Indicates whether or not any grid management measures are in effect.
Hidden if no grid management measures are in effect.
Performance ratio: 87 % Performance ratio is shown if irradiation sensor is available (local or master).
Total CO
2
saved:123 T Lifetime CO
2
emission saved, calculated using configured value.
Total revenue: 234.5 yuan Lifetime revenue, calculated using configured value.
Table 2.2: View 2
2.1.3. Status
Menu Structure - Status
Display Functions Description
[-] Ambient Conditions Only applicable if sensors are connected
Irradiance: 1400W/m
2
Irradiance. “NC” if not connected
PV module temp: 100
o
C
PV module temperature. “NC” if not connected
Ambient temp: 20
o
C
Ambient temperature. “NC” if not connected
Irr. sensor temp: 20
o
C
Irradiation sensor temperature. “NC” if not connected
[-] Photovoltaic
[-] Present values
[-] PV input 1
Voltage: 1000V Voltage detected at PV input 1
Current: 15.0 A Current detected at PV input 1
Power 10000 W Power detected at PV input 1
[+] PV input 2
[+] PV input 3 Not visible if inverter type is 10 kW
[-] Isolation Resistance
Resistance: 45 MΩ PV isolation at start up
[-] PV Input Energy
Total: 369000kWh Daily production of all PV inputs
PV1: 123000 kWh Daily production of PV input 1
PV2: 123000 kWh Daily production of PV input 2
PV3: 123000 kWh Daily production of PV input 3
[-] PV Configuration
PV input 1: Individual
Configuration of PV input 1. The configuration is only shown when the in-
verter is in Connecting or On grid mode.
PV input 2: Individual
PV input 3: Individual
[-] AC-grid
[-] Present Values
[-] Phase 1
Voltage: 250 V Voltage on phase 1
Current: 11.5 A Current on phase 1
Frequency: 50 Hz Frequency on phase 1
Power: 4997 W Power on phase 1
[+] Phase 2
[+] Phase 3
[-] Residual Current Monitor
Current: 350 mA Residual current in mA
[-] Grid management Only visible if enabled by the grid code setting.
[-] Power level adjustment
[-] Present limit: 100 %
Maximum allowed power output in % of nominal power output. “Off”
means that the power level functionality has been disabled in the inverter.
Table 2.3: Status