User Guide DLX Series L00410623-1 79
8.2.1. Modules
Maintain the PV modules as recommended from the manufacturer.
8.2.2. Cables
Regularly check the cables inside and outside for signs of damage or overheating, i.e.
warm conductors or surface corrosion. Replace frayed conductors immediately, find and fix
the reason for the damage!
8.2.3. Electrical Connection
Regularly check that the terminals and plugs are firmly tightened, and that the insulation is
not deteriorated or corroded. If a combiner box is used, also check the terminals and plugs
in the combiner box!
8.2.4. Fuses/Circuit Breakers
Frequently blown fuses or tripped circuit breakers are a clear warning sign of overload,
short circuit or ground fault.
Always determine the reason for blown fuses/tripped circuit breakers prior to
replacement/resetting.
The replacement/resetting must be performed by qualified persons only!
8.2.5. DC Disconnect Switch
To prevent welding of the contacts, thereby extending service life, the DC switch(es) must
be operated at least once every 12 months, preferably at night or when the AC is OFF.
8.2.6. Inverter
It is recommended that the inside of the inverter is checked by the system installer for
humidity and dust every 3 – 4 years.
8.2.7. Ventilation
The heat sink on the back of the inverter conducts heat away from the electronic
components, and must be clean to ensure sufficient cooling performance and thereby
prevent yield losses. This is accomplished by using either: