User Guide DLX Series L00410623-1 25
The configuration of a positive grounded PV string differs from an ungrounded PV
string by the connection of the cables to the DC terminal blocks and the addition of a
grounding strap.
Array configuration depends on the module technology used. Both the positive and
negative DC terminal blocks have three pairs of inputs, which allow three strings to be
connected in parallel. Due to the inverter having one MPP-tracker the PV power should
be identical for every string.
NOTICE
Maximum Voltage: The open circuit voltage, V
OC
, must never exceed 600 V
DC
under any conditions. The voltage generated by PV modules is inversely
proportional to the temperature; at lower temperatures the PV voltage increases
from the nameplate rating and at higher temperatures the PV voltage decreases
from the nameplate rating.
4.3.4.2. Stringbox
The Stringbox is attached to the bottom of the inverter, and provides PV string connection
via the wiring that runs through the plug-in connectors. A DC disconnect switch is
provided and mounted in the Stringbox.
NOTICE
Before removing the lower cover to access the connection terminals ensure that
the DC switch (if supplied) is in the OFF position, and the PV array cables are
disconnected.
Figure 4.3.7: DC disconnect switch
I = ON
0 = OFF