Danfoss L66 Guia do Utilizador Página 22

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 38
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 21
The grey
side of the
ECL Card
Extended service
The grey
side of the
ECL Card
Extended service
32d
Service parameter(s) 17-20 Service parameter(s) 21
32e
17 Influence on desired flow temperature (T
flow.ref(I)
)
Circuit Setting range Factory setting
I OFF / 1 ... 20 K OFF
The desired flow temperature in heating circuit I can be influenced
by an external reference.
OFF: The desired flow temperature in circuit I
is not influenced by any other controller
(slave).
1 ... 20:
The desired flow temperature is increased
by the set value (line 17), if the demand of a
slave is higher.
Temp. Setting line 17
T
flow.ref(I)
T
flow.ref(II)
Time
Example:
If a slave controller demands a higher temperature
than that of the master controller (T
flow.ref(I)
),
the temperature of the master will be increased
accordingly (T
flow.ref(II)
) + the setting (line 17).
The function of line 17 can compensate for heat losses between
master and slave controlled systems.
20 Optimization based on room / outdoor temperature
Circuit
Setting range Factory setting
I
ON / OFF OFF
The optimized start and stop time can be based on either room or
outdoor temperature.
ON: Optimization based on room temperature, if
measured.
OFF: Optimization based on outdoor
temperature. Use this setting if the room
temperature is not measured.
21 Total stop
Circuit Setting range Factory setting
I ON / OFF OFF
Decide whether you want a total stop during the setback
temperature period.
ON: The desired flow temperature is lowered
to 10 °C. The min. setting of the flow
temperature (line 2, section 22) is overruled.
Desired flow
temp. (°C)
10 °C
Time
OFF: No total stop
Desired flow
temp. (°C)
10 °C
Time
Vista de página 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 37 38

Comentários a estes Manuais

Sem comentários