Data sheet ECL Comfort 210 controller and Remote Control Unit ECA 30 / 31
7
VD.KT.W1.02 © Danfoss 04/2010
DEN-SMT/DK
Functions General functions:
• TheECLComfort210hasalltherequired
functions of a modern electronic temperature
controller for heating and DHW applications.
• Thecontrollercanbeusedasmasterorslave
in systems with master / slave ECL Comfort 210
/ 310 controllers.
• TheECLApplicationKeycontainsthe
application software for flexible configuration.
It is possible to update the controller with new
application software.
• TheECLComfort210contains,besidesthe
standard functions, log and alarm functions.
• Thebuilt-inRealTimeClockgivesautomatic
summer / winter time changeover, week and
holiday schedule.
• Motorprotection,whichensuresstablecontrol
and a long life of the motorized control valve,
is available for most of the applications. In
periods without heat demand, the motorized
control valve is exercised to avoid blocking.
• Scheduledcontrolisbasedonaweek
program. A holiday program gives the
possibility to select days with comfort or
saving mode.
• TheECLComfort210canreactonpulsesfrom
a heat or flow meter to limit the power or the
ow.
• Inmanyapplicationsanaloginput(0–10V)
are configured for pressure measuring among
others. The scaling is set in the controller.
• Someapplicationsareconguredtohandle
digital input. This function can be used to have
an external switch to run comfort or saving
mode or react on a flow switch signal e.g.
• Thecontrolparameters,proportionalband
(Xp), integration time (Tn), running time of the
motorized control valve and neutral zone (Nz)
can be set individually for each output (3-point
control).
Heating functions:
• Theheatcurveandmax./min.limitationsof
the flow temperature are set by means of 6
coordinate points.
• Thereturntemperaturelimitationcanworkin
relation to the outdoor temperature or be a
fixed value.
• Theheatingcut-outfunctioncanswitch-out
the heating and stop the circulation pump at
high outdoor temperatures.
• BasedontheroomtemperaturetheECL
Comfort 210 can correct the desired flow
temperature in order to increase the comfort
level.
• Theoptimizerfunctionensuresheatinginthe
desired periods (the lower outdoor
temperature, the earlier cut-in of the heating).
• Therampingfunctionmakesasmoothcut-in
of the heating (district heating installations).
• Theboostfunctionmakesapowerfulcut-inof
the heating (boiler based installations).
• Thecirculationpumpiscontrolledinrelation
to heat demand and frost protection. In
periods without heat demand, the circulation
pump is exercised to avoid blocking.
• Thesavingfunctiongivestwopossibilities:
· reduced flow temperature with fixed
reduction or reduction in relation to outdoor
temperature (the lower the outdoor
temperature, the less the reduction),
· heating off, still with active frost protection
DHW functions:
• TheAutoTuningfunctionfortheautomatic
setting of control parameters for constant
DHW temperature is integrated in the
application A217 and A266. However, Auto
Tuning is only applicable with valves that are
approved for Auto Tuning, i.e. the Danfoss
types VB 2 and VM 2 with split characteristic as
well as logarithmic valves such as VF and VFS.
• Theanti-bacteriafunctioncanfollowa
schedule program.
• TheheatingcircuitcanhaveslidingDHW
priority.
Communication The ECL Comfort 210 has an ECL 485
communication bus, which is used for closed
communication between master, slave and
RCUs.
Additionally, the ECL Comfort 210 has a
non-galvanically separated RS 485 bus for
limited Modbus communication. A USB
connection (type B) will be available for a
Service Tool depending on introduction time.
Master / slave connections
Languages Depending on application, the menu language
is available in English and other languages.