1. Use the factory settings of R
S
which the fre-
quency converter itself chooses on the basis
of the motor nameplate data.
2. The value is stated by the motor supplier.
3. The value is obtained through manual meas-
urements: R
S
can be calculated by measur-
ing the resistance R
PHASE-PHASE
between two
phase terminals. Where R
PHASE-PHASE
is low-
er than 1-2 Ohms (typical for motors > 5.5
kW, 400 V), a special Ohm-meter should be
used (Thomson-bridge or similar). R
S
= 0.5 x
R
PHASE-PHASE
.
4. R
S
is set automatically when AMT has been
completed. See parameter 107 Auto motor
adaption.
109
Stator reactance X
S
(STATOR REACTANCE)
Value:
0.00 - X,XX
Depends on choice of motor
Function:
After setting of parameters 102-106 Nameplate data, a
number of adjustments of various parameters are
made automatically, including stator reactance X
S
.
The shaft performance can be improved by fine-tuning
R
S
and X
S
, see procedure below.
Description of choice:
X
S
can be set as follows:
1. The value is stated by the motor supplier.
2. The value is obtained through manual meas-
urements X
S
is obtained by connecting a mo-
tor to mains and measuring the phase-phase
voltage U
M
and the idle current
.
X
s
=
U
M
I
ϕ
X
L
2
X
L
: See parameter 142.
3. Use the factory settings of X
S
which the fre-
quency converter itself chooses on the basis
of the motor nameplate data.
117 Resonance damping
(resonance damping)
Value:
OFF - 100% [OFF - 100]
OFF % [OFF]
Function:
It is possible to optimise the resonance damping in CT
mode. The grade of the influence is adjusted in this
parameter.
The value may be set between 0% (OFF) and 100%.
100% corresponds to 50% reduction of U/F ratio.
Default value is OFF.
Internal settings (fixed):
The resonance filter is active from 10% of nominal
speed and above.
In this case 5Hz and above.
Speed to go from 0 to nominal flux level: 500ms
Speed to go from nominal to 0 flux level: 500ms
Description of functionality:
The filter monitors the active motor current and
changes the motor voltage according to the figure be-
low. The filter reacts on levels referring to the nominal
motor current.
If the active motor current is below 10%, the motor
voltage will be decreased by the speed mentioned
above until the voltage reaches the setting for Par.
117. If the active motor current comes over 20% the
voltage will be increased by the above mentioned
speed. If the active motor current reaches 40% the
motor voltage will be increased immediately to normal
motor voltage.
The reduction in motor voltage depends on the pa-
rameter 117 setting.
Description of choice:
Set the grade of Motor current [Imact] influence on the
U/F ratio between 0% (OFF) and 100%. 100% corre-
sponds to 50% reduction of U/F ratio. Default value is
OFF.
VLT
®
2800 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
72 MG.27.E3.02 - VLT
®
is a registered Danfoss trademark
Vista de página 71
1 2 ... 67 68 69 70 71 72 73 74 75 76 77 ... 170 171

Comentários a estes Manuais

Sem comentários

Ingersoll-Rand CHOP-CHECK 650941-X-C manuály

Uživatelské manuály a uživatelské příručky pro Čerpadla Ingersoll-Rand CHOP-CHECK 650941-X-C.
Poskytujeme 1 manuály pdf Ingersoll-Rand CHOP-CHECK 650941-X-C ke stažení zdarma podle typů dokumentů: Uživatelský manuál






Další produkty a příručky pro Čerpadla Ingersoll-Rand

Modely Typ Dokumentu
66266-XXX-B Uživatelský manuál   Ingersoll-Rand 66266-XXX-B User Manual, 4 stránky
ARO PD15P-X Uživatelský manuál   Ingersoll-Rand ARO PD15P-X User Manual, 8 stránky
LM2305A-X-B Uživatelský manuál   Ingersoll-Rand LM2305A-X-B User Manual, 4 stránky
670003-X Uživatelský manuál   Ingersoll-Rand 670003-X User Manual, 1 stránky
650717-C Uživatelský manuál   Ingersoll-Rand 650717-C User Manual, 8 stránky
650632-X-C Uživatelský manuál   Ingersoll-Rand 650632-X-C User Manual, 2 stránky
ARO 6661AX-X-C Uživatelský manuál   Ingersoll-Rand ARO 6661AX-X-C User Manual, 8 stránky
TWO-BALL PUMP SERIES 613124-XXX-C Uživatelský manuál   Ingersoll-Rand TWO-BALL PUMP SERIES 613124-XXX-C User Manual, 2 stránky
PD07P-X-X Uživatelský manuál   Ingersoll-Rand PD07P-X-X User Manual, 8 stránky
EXTRUSION PUMP NP623XXXXR8-XX Uživatelský manuál   Ingersoll-Rand EXTRUSION PUMP NP623XXXXR8-XX User Manual, 4 stránky
NP318W01-X Uživatelský manuál   Ingersoll-Rand NP318W01-X User Manual, 4 stránky
NM2328A-X Uživatelský manuál   Ingersoll-Rand NM2328A-X User Manual, 2 stránky
Diaphragm Pump 66610X-X-C Uživatelský manuál   Ingersoll-Rand Diaphragm Pump 66610X-X-C User Manual, 8 stránky
ARO 650542-1 Uživatelský manuál   Ingersoll-Rand ARO 650542-1 User Manual, 4 stránky
TWO BALL PUMP SERIES 650409-X Uživatelský manuál   Ingersoll-Rand TWO BALL PUMP SERIES 650409-X User Manual, 2 stránky
613123-XXX-C Uživatelský manuál   Ingersoll-Rand 613123-XXX-C User Manual, 2 stránky
PH30F-XXX-XXX-C Uživatelský manuál   Ingersoll-Rand PH30F-XXX-XXX-C User Manual, 8 stránky
NP322L01-1 Uživatelský manuál   Ingersoll-Rand NP322L01-1 User Manual, 4 stránky
650715-C Uživatelský manuál   Ingersoll-Rand 650715-C User Manual, 2 stránky
LM2250E-X-B Uživatelský manuál   Ingersoll-Rand LM2250E-X-B User Manual, 4 stránky