6.2.
Communication
[0][Plant, Inverter]
The communication menu contains the following sub menus; see descriptions below. Some of
the menus are only visible in plant view whereas others are only visible in inverter view.
6.2.1.
RS485
[0] [Inverter]
Illustration 6.4: RS485 Network Address
Change the RS485 network address of the inverter here. Ensure that each inverter in the net-
work has a unique address.
The RS485 addresses must be selected within the following range (network.subnet.address):
2.1.1 to 12.14.254.
Note:
Only in very rare cases will it be necessary to change the RS485 address of the inverter as
each inverter is delivered with a unique RS485 address.
6.2.2.
IP Setup
[0] [Inverter]
The TripleLynx CN Pro inverter is equipped with two integrated Ethernet interfaces, which con-
nectivity to Ethernet networks.
The inverter automatically configures a unique IP address.
An integrated DNS server enables access to the master inverter via its name or serial number.
For local administration of IP addresses, the inverter also supports DHCP in the automatic con-
figuration.
Alternatively, IP addresses can be administrated manually under [Setup Communication IP
setup].
View the inverter IP address via the display at [Setup Communication setup IP setup].
Note:
For manual configuration, ensure that each inverter has a unique IP address.
6. Setup
30 L00410583-01_02
6