Danfoss DHP-AX Especificações Página 1

Consulte online ou descarregue Especificações para Bombas de calor Danfoss DHP-AX. Danfoss DHP-AX Specifications [en] [es] [fr] Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 0
VMBMH302
Danfoss DHP-AX
Installation and Service instructions
Vista de página 0
1 2 3 4 5 6 ... 69 70

Resumo do Conteúdo

Página 1 - Danfoss DHP-AX

VMBMH302Danfoss DHP-AXInstallation and Service instructions

Página 2 - © 2009 Copyright Danfoss AS

10 – Installation VMBMH3023.3 Supplied contents3.3.1 Control1. Check that there is no transport damage. 2. Remove the packaging and check that the

Página 3

Installation – 11VMBMH3024 Unpacking and installation4.1 Assembling the stand (accessory) NOTE! Only place the heat pump on its short side as sh

Página 4 - 2 Safety precautions

12 – Installation VMBMH3025 Piping installation NOTE! To prevent leaks, ensure that there are no stresses in the connecting pipes! NOTE! It i

Página 5 - 2.4 Electrical connection

Installation – 13VMBMH3025.1.1 DHP-AX, VL systemFigure 7: General connection diagram.Position Name5 DHP-AX heat pump18 Water heater (accessory)21

Página 6 - 2.5 Commissioning

14 – Installation VMBMH3026 Electrical Installation Electrical current! The terminal blocks are live and can be highly dangerous due to the risk

Página 7 - Installation instructions

Installation – 15VMBMH302 When the cable is connected to the terminal block a screwdriver is used to open the terminal block, see fig-ure below. F

Página 8 - 3 Heat pump information

16 – Installation VMBMH302In the event of a surplus of heat the conditions are the opposite:ROOM FACTORIncreased room tempe-rature, °CActual room temp

Página 9 - 3.2 Technical data DHP-AX

Installation – 17VMBMH3028.3 Manual testTest operate and at the same time check the function of the tested components.8.3.1 Activate MANUAL TEST1.

Página 10 - 3.5 Space requirement

18 – Installation VMBMH302Follow the instructions below to perform a calibration.1. Detach and remove any insulation by the sensor to be calibrated.2

Página 11 - 4 Unpacking and installation

Installation – 19VMBMH30210 Customer informationAfter installation and test operation, the customer must be informed about their new heat pump instal

Página 12 - 5 Piping installation

2 – Service VMBMH302These instructions are valid for the following model of Danfoss heat pump:DHP-AXIf these instructions are not followed during inst

Página 13

20 – Service VMBMH302Service instructions

Página 14 - 6 Electrical Installation

Service – 21VMBMH30211 The heat pump11.1 Function descriptionA heat pump utilises the free energy from the sun and that is found in a natural heat s

Página 15 - 7 Installing accessories/

22 – Service VMBMH30211.2 Heating and defrost functions11.2.1 HeatingDHP-AX is a heat pump that can produce heating for houses and water heaters. Ho

Página 16 - 8 Checking the installation

Service – 23VMBMH30211.2.2 Defrost functionDuring operation the air heat exchanger is cooled by the energy exchange at the same time as the humid-ity

Página 17 - 8.3 Manual test

24 – Service VMBMH302The heat pump unit consists of the following basic units: 1 Heat pump unit Compressor 2-way expansion valve Condense

Página 18 - 9 Start-up and commissioning

Service – 25VMBMH302At outdoor temperatures colder than 0°C, supply water hotter than 40°C is sent out to the heating system and at outdoor temperatur

Página 19 - 10 Customer information

26 – Service VMBMH302Figure 22: The adjusted curve at -5°C Sometimes, at outdoor temperatures between -5°C and +5°C, part of the heat curve may need a

Página 20 - Service instructions

Service – 27VMBMH302The integral value is a measurement of the surface under the time axle and is expressed in degree minutes. The figure below shows

Página 21 - 11 The heat pump

28 – Service VMBMH30211.5.9 DEFR CURVETo start defrosting the outdoor unit, the control system makes a calculation using the temperature of the incom

Página 22

Service – 29VMBMH30212 Control panel12.1 Function descriptionThe heat pump has an integrated control system that is used to automatically calculate

Página 23 - 11.3 Components

Installation – 3VMBMH3021 About the instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.1 Introduction . . .

Página 24 - 11.5 Important parameters

30 – Service VMBMH302The indicator at the bottom of the control panel has two modes: Lit continuously, the heat pump has power and is ready to pro

Página 25

Service – 31VMBMH302Symbol MeaningDEFROST Displayed when defrosting is active.FAN Displayed when the fan is active.12.2.4 Operational informationShow

Página 26

32 – Service VMBMH30213 Menu information13.1 INFORMATION menuThis menu is used to change the heat pump’s operating modes and adjust the heat curve.

Página 27

Service – 33VMBMH30213.1.1 Sub menu INFORMATION -> OPERATIONUsed to select operating mode.Menu selection Meaning Factory setting (OFF)The installa

Página 28

34 – Service VMBMH302Menu selection Meaning Factory settingPOOL (Expansion card)Only appears if POOL is selected. The temperature in the pool is contr

Página 29 - OPERAT. AUTO

Service – 35VMBMH30213.1.5 Sub menu INFORMATION -> OPERAT. TIMEUsed to show the operating time for each component. Time given in hours.Menu select

Página 30 - 12.2 Display

36 – Service VMBMH30213.2 SERVICE menuThis menu is for use during installation and service to optimise and adjust the operation of the heat pump. Ope

Página 31 - Message Meaning

Service – 37VMBMH30213.2.1 Sub menu SERVICE -> HOT WATERUsed to change the settings for hot water production.Menu selection Meaning Factory settin

Página 32 - 13 Menu information

38 – Service VMBMH302Menu selection Meaning Factory settingHYSTERESIS If the difference between the actual supply temperature and the calculated suppl

Página 33

Service – 39VMBMH30213.2.5 Sub menu SERVICE -> INSTALLATIONUsed for settings that are set during installation.Menu selection Meaning Factory setti

Página 34

4 – Installation VMBMH3021 About the instructions1.1 IntroductionThese instructions are split into two parts: installation instructions and service

Página 35

40 – Service VMBMH302Menu selection Meaning Factory settingVERSION Shows the software version which is stored on the display card respectively the I/O

Página 36 - 13.2 SERVICE menu

Service – 41VMBMH302

Página 37

42 – Service VMBMH30214 Noise information14.1 Flexible hosesAll pipes should be routed in such a way that vibrations cannot be transmitted from the

Página 38

Service – 43VMBMH30214.2 Preventative measuresSome of the following points can also be used when troubleshooting. Do not install heat pumps on wa

Página 39

44 – Service VMBMH30215 Troubleshooting15.1 AlarmShown in display in the event of an alarm. To reset alarms 1-5, set the operating mode to OFF or cu

Página 40

Service – 45VMBMH30215.2 Measurement pointsConversion table for sensors When reading the resistance of the sensors, the sensor leads must first b

Página 41 - Service – 41VMBMH302

46 – Service VMBMH302Break pressure pressure switchesRefrigerant Pressostat Break pressureR407C Low pressure pressostat 0.08 MPaOperating pressure swi

Página 42 - 14 Noise information

Service – 47VMBMH302Cause Troubleshooting Remedy8. Incorrect mix of anti-freeze, the concentration must be in accordance with instructions. Check the

Página 43 - 14.2 Preventative measures

48 – Service VMBMH302Cause Troubleshooting Remedy15. Blocked evaporator on the refrigerant side. Using manometer apparatus and ther-mometer, check tha

Página 44 - 15 Troubleshooting

Service – 49VMBMH302Cause Troubleshooting Remedy9. External system shunt that clo-ses on time setting. Check for shunts or valves in the system, which

Página 45 - 15.3 Check points

Installation – 5VMBMH302 Bleed valves must be installed where necessary. Radiator systems with closed expansion tanks must also be supplied wi

Página 46 - 15.4 Operational problems

50 – Service VMBMH302Problem – Alarm MS (motor protection)Cause Troubleshooting Remedy1. Phase drop or blown fuse. Check that all phases are present

Página 47 - Cause Troubleshooting Remedy

Service – 51VMBMH302Problem – Incorrect phase sequenceCause Troubleshooting RemedyThe incoming phases have the incorrect sequence (only applies to 3-p

Página 48

52 – Service VMBMH302Cause Troubleshooting Remedy2. Brine temperature too low. Check the set value on ALARM BRINE in the heat pump’s control computer

Página 49

Service – 53VMBMH302Cause Troubleshooting Remedy4. Overheating too high. Using manometer apparatus and ther-mometer check what the overheating readin

Página 50 - Problem – Alarm sensor (all)

54 – Service VMBMH302Cause Troubleshooting Remedy11. Leak at soldered joint on water heater. Locate the leak. If there is a leak at the soldered joint

Página 51

Service – 55VMBMH302Problem – Loud compressor noiseCause Troubleshooting Remedy1. Phase drop.The compressor attempts to start or operates on two phase

Página 52

56 – Service VMBMH30215.4.4 Hot waterProblem – Temperature and/or quantityCause Troubleshooting Remedy1. Defective 3-way valve motor. Check the func

Página 53 - Problem – Leak fluid side

Service – 57VMBMH302Cause Troubleshooting Remedy10. Heat loss in the hot water pipe. Open the hot water tap, read off the tem-perature on the outgoing

Página 54 - 15.4.3 Noise

58 – Service VMBMH302Cause Troubleshooting Remedy6. The heat pump has stopped on HIGH RETURN. • Check what the MAX RETURN value is set at in the heat

Página 55

Service – 59VMBMH302Cause Troubleshooting Remedy12. Changed conditionsHave you increased your heating and/or hot water demand? • If the heat pump has

Página 56 - 15.4.4 Hot water

6 – Installation VMBMH302 Hazardous electrical voltage! The terminal blocks are live and can be highly dangerous due to the risk of electric shock

Página 57 - Problem – Too cold

60 – Service VMBMH302Problem – irregular indoor temperatureCause Troubleshooting Remedy1. The heat pump’s control com-puter is not set/adjusted to the

Página 58

Service – 61VMBMH302Problem – Runs on electric heating elementCause Troubleshooting Remedy1. Operating mode AUX. HEATER is selected. If this operating

Página 59 - Problem – Too hot

62 – Service VMBMH302Problem – The auxiliary heater is in operation but not the compressorCause Troubleshooting Remedy1. Operating mode AUX. HEATER is

Página 60 - 15.4.6 Other

Service – 63VMBMH302Cause Troubleshooting Remedy7. The compressor runs backwards. The incoming phases have the incorrect sequence (only applies to 3-p

Página 61

64 – Service VMBMH302Cause Troubleshooting Remedy7. The heat pump has stopped on HIGH RETURN. • Check what the MAX RETURN value is set at in the heat

Página 62

Service – 65VMBMH302Cause Troubleshooting Remedy12. Overfilled refrigerant circuit. Using manometer apparatus and ther-mometer, check that the unit’s

Página 63

66 – Service VMBMH302Cause Troubleshooting Remedy5. Changed conditions Have you increased your heating and/or hot water demand? • If the heat pump has

Página 64

Service – 67VMBMH30215.4.7 Outdoor unitProblem – Noise/loud noiseCause Troubleshooting Remedy1. Positioning the outdoor unit. Determine whether the

Página 65

68 – Service VMBMH302

Página 66

Service – 69VMBMH302

Página 67

Service – 7VMBMH302Installation instructions

Página 69 - Service – 69VMBMH302

8 – Service VMBMH3023 Heat pump information3.1 DHP-AX3.1.1 Dimensions and connectionsThe stand shown in the image is an accessory.Figure 1: DHP-AX,

Página 70 - VMBMH302

Service – 9VMBMH3023.2 Technical data DHP-AXDHP-AX 6 8 10 12R407C R407C R407C R407C1,6 1,6 2,5 2,73,4 3,4 3,4 3,43,1 3,1 3,1 3,1400 400 400 4002,0 2,

Comentários a estes Manuais

Sem comentários